Protection Plan Reviews

Get your fire protection system plans reviewed, approved and permitted.

Every fire protection system in Enid, required or voluntary, needs an approved plan and a permit before work starts. An approved third-party consultant does the technical review.

Before you start

No work is to be performed on the proposed systems until plans are approved and a permit issued.

Plan review and inspection fees are paid directly to the independent consultant. Enid Fire Department plan review and inspection fees are waived.

Required NFPA standards

Fire protection systems, whether required by adopted code or voluntary, non-required systems shall be installed in accordance with the most-current and appropriate referenced NFPA standard as follows:

Fire protection systems and the NFPA standard each must follow
System Standard and edition
Portable fire extinguishers NFPA 10, 2013 Ed.
Automatic fire sprinkler systems NFPA 13, 2016 Ed.
Automatic fire sprinkler systems: one- and two-family dwellings NFPA 13D, 2016 Ed.
Automatic fire sprinkler systems: residential occupancies (4 stories or fewer) NFPA 13R, 2016 Ed.
Standpipe and hose systems NFPA 14, 2016 Ed.
Water spray fixed systems NFPA 15, 2017 Ed.
Dry chemical extinguishing systems NFPA 17, 2017 Ed.
Wet chemical extinguishing systems (UL 300) NFPA 17A, 2017 Ed.
Installation of stationary fire pumps NFPA 20, 2016 Ed.
Automatic fire alarm systems NFPA 72, 2016 Ed.

How plan review works

  1. Step 1

    Send plans to an approved consultant. Submit construction plans and specifications to an approved, independent fire protection engineer or consultant for a preliminary review, technical opinion and report.

  2. Step 2

    The consultant reviews your plans. The consultant keeps a copy and forwards the remaining copies to the Fire Marshal with the technical opinion and report.

  3. Step 3

    The Fire Marshal approves and issues a permit. On final approval, the Fire Marshal returns copies to the contractor or owner with notes for corrections or additions and approval signatures, and issues a permit for construction and installation.

  4. Step 4

    The consultant inspects the work. Whenever possible, the consultant also conducts 50% progress inspections and final inspections to verify the installation matches the reviewed plans and standards.

International Fire Code 104.7.2, Technical Assistance

To determine the acceptability of technologies, processes, products, facilities, materials and uses attending the design, operation or use of a building or premises subject to inspection by the fire code official, the fire code official is authorized to require the owner or owner’s authorized agent to provide, without charge to the jurisdiction, a technical opinion and report. The opinion and report shall be prepared by a qualified engineer, specialist, laboratory or fire safety specialty organization acceptable to the fire code official and shall analyze the fire safety properties of the design, operation or use of the building or premises and the facilities and appurtenances situated thereon, to recommend necessary changes. The fire code official is authorized to require design submittals to be prepared by, and bear the stamp of, a registered design professional.

Approved third-party consultants

Fire Protection Consulting, Inc.

J.C. Carroll

4709 Roundup Road, Edmond, OK 73034
Phone: 405-509-2157
Cell: 405-250-4296
fire_consult@cox.net

Florian Protective Services, LLC

Adam Stuckey

6608 N. Western Ave., Suite 277, Oklahoma City, OK 73116
Phone: 405-312-7250
Cell: 405-595-7350
astuckey@florianprotective.com
Florian Protective Services website

Paradigm Engineering, PLLC

Lance D. LaRue

P.O. Box 204, Choctaw, OK 73020
Phone: 405-306-1400
llarue@pbsengineering.com
PBS Engineering website

Other independent third-party technical consultants may be used with the consent and approval of the Fire Marshal.

What to send the reviewer

Option 1: Four paper sets

  • One copy to be retained by the third-party technical consultant.
  • One copy to be retained by the Office of the Fire Marshal.
  • Two copies (with notes and approval signatures) to be returned to contractor/owner.
  • One copy shall be delivered and retained at the job site during construction/installation.

Option 2: Two paper sets plus digital files

Provide two hard copy sets along with digital (.pdf) files on disc or USB thumb-drive media to be used by the technical consultant and file copy for the Fire Marshal. The two hard copy sets will be signed and returned for contractor and job-site copies.

Permits and licensing

International Fire Code 105.4.6

“One set of approved construction documents shall be returned to the applicant, and said set shall be kept on the site of the building or work at all times during which the work authorized thereby is in progress.”

Permits can be revoked

Fire protection system permits can be revoked by the Fire Marshal of the City of Enid and are contingent on following all adopted codes and ordinances of the City of Enid pertaining to proper installation.

State license required

Fire protection industry workers must be properly licensed by the State of Oklahoma. Workers may be required to show licenses to fire code official.

  

Questions about plan review?